HOMEProductsPLCPLC replacement







Base Kit ZW-160BK for replacement of W16 -> JW20H/30H (MTO)

Conventional I/O, power source wiring, set up environment etc. can be used as base kits for JW20H/30H series when replacing W16 series with JW20H/30H series.

W16 series and JW20H/30H series require different I/O specifications, however, we will be able to provide all required items, including wiring within the base kits. (JW20H/30H will be built in to ZW-160BK base kits for replacement of W16 -> JW20H/30H.)


Connection port conversion unit for replacement of ZW -> JW
JW-101ZT/102ZT/103ZT/104ZT/105ZT/106ZT/107ZT


These connection port conversion units enable connection with JW series and do not require the replacement of the ZW terminal block with existing wiring.

These can bring about work improvement in I/O wiring and replacement process.




Model Recommended I/O module
ZW series -> JW series
JW-101ZT
ZW-32N1T
ZW-32N2T
-> JW-31N
JW-32N
JW-102ZT
ZW-32S1T *1
-> JW-33S
JW-103ZT
ZW-32S2T
ZW-32S2TD *2
ZW-32S5T
-> JW-32S
JW-32S
JW-35S
JW-104ZT
ZW-32S4T
-> JW-34S
JW-105ZT
ZW-16S4
-> JW-34S *3
JW-106ZT
ZW-16N1
ZW-16N2
ZW-16N3
ZW-16S1
ZW-16S3
-> JW-11N
JW-12N
JW-13N
JW-13S
JW-13S
JW-107ZT
ZW-16S2
-> JW-12S

*1 Not applicable when the COMM wiring of ZW-32S1T is 8 points per COMM and uses separate power source.
(COMM wiring will be short-circuited to 16 points per unit inside the connection port conversion unit.)
*2 Not applicable when POW 1 and POW2 of ZW-32S2TD uses different power source.
(POW1 and POW2 will be short-circuited within the connection port conversion unit.)
*3 When connected to JW-34S, first 16points will be effective, however, the I/O will occupy 32points.
(I/O address, after connected to JW-34S, will shift by 16points, therefore, program change will be necessary.)
(Converting JW-34S to unit per 16points is possible. For more details, please consult with our customer support center near you.)